There is no vaccine against legionellosis, and antibiotic prophylaxis is not effective. Travelers at increased risk for infection, such as the elderly or those with immunocompromising conditions such as cancer or diabetes, may choose to avoid high-risk areas, such as whirlpool spas.
Temperature affects the survival of Legionellae as follows:[1]
- 70 to 80 °C (158 to 176 °F): Disinfection range
- At 66 °C (151 °F): Legionellae die within 2 minutes
- At 60 °C (140 °F): Legionellae die within 32 minutes
- At 55 °C (131 °F): Legionellae die within 5 to 6 hours
- Above 50 °C (122 °F): They can survive but do not multiply
- 35 to 46 °C (95 to 115 °F): Ideal growth range
- 20 to 50 °C (68 to 122 °F): Legionellae growth range
- Below 20 °C (68 °F): Legionellae can survive but are dormant
Removing slime is an effective control process, because up to 1,500 times more chemicals are needed to kill bacteria in slime than free floating bacteria[2] [3].
The European Working Group for Legionella Infections (EWGLI)[4] was established in 1986 within the European Union framework to share knowledge and experience about potential sources of Legionella and their control. This group has published guidelines )[5] about the actions to be taken to limit the number of colony forming units (i.e., the aerobic count) of micro-organisms per mL at 30 °C (minimum 48 hours incubation):
Aerobic count | Legionella | Action required |
---|---|---|
10,000 or less | 1,000 or less | System under control. |
more than 10,000 up to 100,000 |
more than 1,000 up to 10,000 |
Review program operation. The count should be confirmed by immediate re-sampling. If a similar count is found again, a review of the control measures and risk assessment should be carried out to identify any remedial actions. |
more than 100,000 | more than 10,000 | Implement corrective action. The system should immediately be re-sampled. It should then be ‘shot dosed’ with an appropriate biocide, as a precaution. The risk assessment and control measures should be reviewed to identify remedial actions. |
Aerobic count, cfu/ml at 30°C (minimum 48 hours incubation). Colony count determined by pour plate method according to ISO 6222(21) or by spread plate method on yeast extract agar
Legionella, bacteria cfu/litre. Determined in accordance with ISO 11731(20).
Expect to find Legionella CFUs because almost all natural water sources, contain Legionella. Legionella samples need to be run within 24 hours. Samples should be kept cold with ice packs, but not frozen, and should remain up right.
Many governmental agencies, cooling tower manufacturers and industrial trade organizations have developed design and maintenance guidelines for preventing or controlling the growth of Legionella in cooling towers. Below is a list of sources for such guidelines:
The guidance issued by the UK government's Health and Safety Executive (HSE) now recommends that microbiological monitoring for wet cooling systems, using a dip slide, should be performed weekly. The guidance now also recommends that routine testing for legionella bacteria in wet cooling systems be carried out at least quarterly, and more frequently when a system is being commissioned, or if the bacteria has been identified on a previous occasion. [6]
The City of Garland, TX requires yearly testing for legionella bacteria at Cooling towers at apartment buildings. [7]
Malta requires twice yearly testing for legionella bacteria at Cooling towers and water fountains. Malta prohibits the installation of new cooling towers and evaporative condensers at health care facilities and schools. [8]